Part Number:
ETI0001-1452
NSN: 6130-01-544-3472
Ultra Compact Rugged Mil Spec® 4000 VA
Integrated Rackmount UPS and Intelligent
Power Distribution Unit Combination
P/N:
ETI0001-1452, USNavy Standard for NSSN,
Ultra Compact Military Power® IsolatedMil Spec UPS,
4000 VA Rugged Rack Mount UPS w/ PFC, Drawout Battery and
Integrated 6 Circuit, Intelligent, Solidstate Power Distribution Unit
P/N:
ETI0001-1452 Rugged Mil Spec UPS andPDU Standard Front
Panel Layout w/ Drawout Battery Module
NSN: 6130-01-544-3472
P/N:
ETI0001-1452 Rugged Mil Spec UPS and PDU Standard Rear
Panel Layout
Optional P/N:
ETI0001-0876 UPS and PDU Remote Control Panel in 1U
The field proven Military Power® UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.These units are equally suited for use in shipboard, airborne, vehicular, fielddeployed or fixed locations with controlled or uncontrolled environments. The
ETI0001-1452 was specifically designed for US NavyNSSN Virginia Class Submarine rack systemsrequiring higher power requirements using minimal rack space. The
ETI0001-1452 does not require a separate PDU since the PDUfunctions are already integrated into the UPS module. This saves rack space,cabling and expense while improving overall reliability.
This heavy-duty chassis occupies only 4U (7.0") of rack space whileaccommodating a front drawout, hot-swap battery module. The chassis has roundedmetal corners and rugged handles, both front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to preventdamage due to shock and vibration in any axis. These units can be mountedhorizontally or vertically.
The internal shieldedinput transformer provides galvanic isolation with provisions for domestic (115VAC, CONUS) and optional autoranging international input voltages (85-270 VAC,OCONUS). Theunit also operates as a frequency converter, taking 46-70 hertz input and converting it to 60 hertz power. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The inputcircuit breaker and the galvanic isolation transformerall provide a double pole isolated source for all installations including shipboard systems oroverseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm canbe heard in high noise environments.All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to preventdamage or accidental operation. The internal intelligent PDU allows control ofthe individual output circuits incorporating thermal and interlock interfacesfor additional control and safety, plus Battleshort override. The display andcontrol panel can be mounted remotely in the rack at eye level, or on the keyboard console,or on the unit front panel with only a logic level cable connection.
The rear panel provides locking connectors for the input and output power with various optional configurations available. The output connectors are unique allowing the use of either standardNEMA 5-15P plugs or MS threaded metal shell connectors. This reverse air flow version draws air through the front and exhausts out the rearvents into the rack. A removable and washable intake air filter and high capacity stainless steel ballbearing fans provide added protection in both controlled and hostile environments. The
ETI0001-1452 has the added benefit of having afield replaceable battery via a front drawout battery module. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. Afrequency selection switch is available for those sites requiring 50 hertz output insteadof the standard 60 hertz. The Status connector provides aninterface with optional computer software providing loss of AC and low battery status as well asremote shut down capability. The PDU Remote Control connector provides aninterface to optional remote display/control panels.
See the Power Distribution Units section for a listing of stand alone PDUs. See the N3 Series UPS section for UPS withoutthe integrated PDU and remote control.
Overall, the Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction
AC OUTPUT | |
Output voltage: | 120 VAC true sinewave standard, others optional |
Output rating: UPS | 4000 VA standard in 4U chassis x 26" deep 0.65 to 0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 or 50 Hz ± 2.5% synchronized to utility 60 or 50 Hz ± 1.0% w/ utility not available 400 or 1000 Hz output available as an option |
Operational status | Status, load and battery level LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT | |
Input voltage selection: | Nominal 115 VAC, optional autoranging input of 85-270 VAC |
Input voltage tolerance: UPS | 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load |
Input frequency: | From 46 Hz to 70 Hz standard, optional to 440 Hz |
Input power factor: | Better than 99% typically |
Input/output isolation: | 4000 VA, up to 120 dB common mode, <1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole input breaker w/ UPS fuses Optional cold start to turn on w/o AC present |
Input power connection: | MS 3102A-22-2P, 3 pin, locking |
INTERNAL BATTERY | |
Internal battery type: | Maintenance free immobilized electrolyte, Flame retardant materials, Oxygen Index 28+ |
Internal battery life: | Rated for continuous service life of 5 years |
Internal DC protection: | Panel mounted fuses standard, breaker optional |
Internal battery replacement: | Drawout module from rear of unit |
External battery expansion: | Up to 24 hours w/ optional Battery Expansion Modules |
DISTRIBUTION PANEL | |
Output circuits: | Seven controlled outputs via solidstate relays |
Output control: | Local/remote control panel w/rocker switches Thermal and remote interlock ON/OFF control |
Output receptacles: | MS / NEMA 5-15R threaded locking, various options |
MECHANICAL | |
Dimensions ( H x D x W ): UPS | 7.0 (4U) x 26.0 x 19.0 in (178x660x483mm) |
Rack Slide Mount Patterns: | Jonathan, General Devices patterns standard, others optional |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Shipping weight: Total UPS w/o Battery Module Drawout Battery Module |
170 lb. ( 77 kg) with lift handles front and rear 104 lb. ( 47 kg) with lift handles front and rear 66 lb. ( 30 kg) with lift handles front |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, positive pressure, forced air |
Cooling air direction: | Front intake, exhaust to rear |
Air intake filter: | Washable metal filter media, others optional |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: | 32° to 113° F ambient (0° to 45° C ), lower/ higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optional |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Cold Start, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits |