PersonalSource™ Desktop UPS
1500 VA, 2000 VA and 3000 VA
PersonalSource 600 to 3000 VA Front Views
True On-line Design
A recent Bell Laboratories study indicates that blackouts account for less than 5% of power disturbances. The other 95% consist of surges, noise, sags and brownouts. Equipment connected to utility power experiences an average of 128 such events each month. These events can disrupt proper operation of sensitive computer based equipment, decreasing productivity and creates unnecessary production, service and data recovery costs.
A True On-line UPS is the only design that can provide the maximum protection against major power problems. This is accomplished through converting the incoming AC utility voltage to a DC voltage. From this DC voltage, an AC voltage is then completely regenerated by the UPS, providing a clean, well-regulated source to your equipment, thereby eliminating power related problems. This solidstate generator sets the True Regenerative On-Line UPS apart from all other Line-interactive and Off-line designs, which leave your sensitive equipment connected directly to the dirty utility power 99+% of the time. If your equipment is operating in a “Mission Critical” application, then you need a True On-line UPS and the PersonalSource is the best choice in True On-line UPS technology.
Input Power Factor Correction
All PersonalSource Series models include state of the art Input Power Factor Correction. This greatly reduces the amount of current demanded from your building wiring system, yielding an efficient, “building friendly” UPS.
Microprocessor Control
The PersonalSource UPS incorporates advanced microprocessor technology. This technology makes possible a high level of internal UPS control as well as system information, data logging, self-diagnostics, SNMP and enhanced computer communication through any RS-232 port.
SNMP/HTTP Remote Management Support
An optional SNMP/HTTP Agent board is available for direct installation into all PersonalSource models. The SNMP/HTTP Agent provides for direct connection of the UPS to any 10Base2 or 10BaseT Ethernet LAN.
Overall, the PersonalSource Series is uniquely qualified for critical systems combining advanced modular design features with highly reliable construction.
Technical Specifications:
PART NUMBER: |
ETI0015 |
ETI0015 |
ETI0015 |
ETI0015 |
ETI0015 |
ETI0015 |
||
INPUT |
Nominal Voltage: |
120 VAC |
230 VAC |
120 VAC |
230 VAC |
120 VAC |
230 VAC |
|
Voltage Range: |
87-140 V |
170-255 V |
87-140 V |
170-255 V |
87-140 V |
170-255 V |
||
Current (max): |
11 A |
5.9 A |
14 A |
7.6 A |
21 A |
11.6 A |
||
Frequency: |
50/60 Hz ±5% |
|||||||
Efficiency: |
>86% |
|||||||
Power Factor: |
>0.95 |
|||||||
OUTPUT |
VA Rating: |
1500 VA |
2000 VA |
3000 VA |
||||
Power5 |
1050 W |
1400 W |
2100 W |
|||||
Voltage |
110 VAC |
220 VAC |
110 VAC |
220 VAC |
110 VAC |
220 VAC |
||
115 VAC |
230 VAC3 |
115 VAC |
230 VAC6 |
115 VAC |
230 VAC6 |
|||
120 VAC3 |
240 VAC |
120 VAC6 |
240 VAC |
120 VAC6 |
240 VAC |
|||
Frequency: |
50/60 Hz (auto tracking) |
|||||||
Voltage Regulation: |
±2% |
|||||||
Frequency Stability: |
±0.3% (Battery mode) |
|||||||
Step Load Change: |
±7% for 100% load variation |
|||||||
Harmonic Distortion: |
Linear Load <3% |
|||||||
Overload: |
105% load for 50 seconds |
|||||||
Crest Ratio: |
3:1 |
|||||||
BATTERY3 |
DC Voltage: |
72 VDC |
96 VDC | |||||
Type: |
Maintenance Free, Valve Regulated, Sealed Lead Acid, Flame Retardant, Absorbed Electrolyte |
|||||||
Backup time |
Full Load |
11 minutes typically |
7 minutes typically |
5.5 minutes typically |
||||
Recharge Time: |
8 Hours to 90% |
|||||||
Transfer Time |
Line Fails/Recovers: |
Zero time – true online, no transfer for brownout or blackout |
||||||
UPS - Bypass/Reverse: |
<4 ms for bypass transfers |
|||||||
After Overload: |
Auto Transfer to UPS |
|||||||
Audible Noise |
@ 1 Meter |
<55 dBA |
||||||
Indicators |
LEDs: |
Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level |
||||||
Audible Alarms |
|
DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temperature, Over Load, Alarm. |
||||||
Interface |
Computer: |
UPS industry style RS-232 |
||||||
Environment |
Temperature: |
0°C – 40°C (32°F – 104°F) |
||||||
Humidity: |
10% - 95% Non-condensing |
|||||||
Mechanical |
Input Line Cord: |
6 Foot Cord with |
6 Foot Cord with |
6 Foot Cord with |
||||
6 Foot Cord with |
6 Foot Cord with |
6 Foot Cord with |
||||||
Output Receptacles: |
(6) NEMA 5-15R |
|||||||
(6) IEC320 |
||||||||
Weight |
68.4 lbs (31kg) |
68.4 lbs. (31kg) |
81.4 lbs. (37kg) |
|||||
Dimensions Inches: |
13.8 x 7.6 x 18.9 |
13.8 x 7.6 x 18.9 |
13.8 x 7.6 x 18.9 |
|||||
Approvals |