Part Number:
ETI0001-1233
NSN: 6130-01-458-1080
NSN: 6130-01-516-2403
NSWC Rugged Mil Spec 2000 VA UPS
120 VAC and 28 VDC Power Source with
Dual Source Input and Cold Start
Naval Surface Warfare Center ControlSystem
Rugged Mil Spec Rack or Fixed Mount 2.0 kVA AC and DC UPS W/Dual Source Input and External Battery Module
P/N:
ETI0001-1233 Rugged Mil Spec UPS Standard Front Panel Layout
with 2U Battery Shown in Fixed Mount (Deck Mount) Configuration
NSN: 6130-01-458-1080
NSN: 6130-01-516-2403
P/N:
ETI0001-1233 Rugged Mil Spec UPS Standard Rear Panel Layout with 2U BatteryNSN: 6130-01-458-1080
The field proven Rugged Power UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, ruggedconstruction, compact size and light weight design. These units are equallysuited for use in shipboard, airborne, vehicular, field deployed or fixedlocations with controlled or uncontrolled environments.The
ETI0001-1233 is being used by Naval Surface Warfare Center as thepower source for critical ship controls because of the stringent performanceand reliability requirements.
The heavy-duty chassis, occupying only 5.25”(3U) for the electronics and 3.5" (2U) for the battery module by 23.5” depth, has rounded metal corners and rugged handles frontand rear, aiding in safe handling. Internally, all major components are wellsecured and electrically insulated to prevent damage due to shock andvibration.
The internal shieldedinput transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) inputvoltages. Forfield deployed scenarios, the Cold Start feature allows the unit to run from itsbattery module before external AC is available. SpecialEMI/RFI filtersand input power factor correction minimize both input current and harmonics. Toprovide added flexibility and reliability, the
ETI0001-1233 accepts two independentAC power sources and includes inrush current limiting. TheUPS can operate from either power source automatically and does not use itsbattery unless both sources have failed.
Theunit also operates as a frequency converter, taking 46-70 hertz input and converting it to clean, uninterruptible 60 hertz power. The
ETI0001-1233 has theadded benefit of having an internally redundant 28 VDC DC power source output.
The LED arrays keep the operatorinformed as to the unit's status including load and battery levels. Thehigh intensity audible alarm can be heard in high noise environments. Allcontrols and protective devices are brought to the front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed toprevent damage or accidental operation. Theinput switch and the galvanic isolation transformerall provide a double pole isolated source for all installations including shipboard systems oroverseas locations where phase references and grounding are not consistent.
The rear panel provides locking connectors for the inputand output power. Removable and washable air filters and a high capacity stainless steel ballbearing fan provide added protection in both controlled and hostileenvironments. The exhaust air is diverted out the front vents, withalternate air flow directions optional. The external battery connector allows the safe and easy addition ofthe standard or extra battery modules without having to shut the unit down.The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. TheStatus connector provides an interface with optional computer softwareproviding loss of AC and low battery status as well as remote shut down capability.
See
ETI0001-1233AA for a newer upgraded version of this unit that is totally backward compatible.See the Power Distribution Units section for alisting of stand alone PDUs. See the N5 Series section forversions of UPS with an integrated PDU and remote control.
Overall, the Rugged Power line is uniquely qualified for criticalshipboard, vehicle, airborne or land based systems combining advanced modular designfeatures with highly reliable construction.
AC OUTPUT | |
Output voltage: | 120 VAC true sinewave standard, up to 600 VAC optional |
Output rating: UPS | 2000 VA 0.65-0.75 pf standard including DC output |
Non-linear load capacity: UPS | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: UPS | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: UPS | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 1.0% independent of input frequency 50, 400 or 1000 Hz output available as an option |
Operational status | Status, load and battery LEDs, w/contacts +90 dB audible alarm, alarm on/off inhibited |
DC OUTPUT | |
Output voltage / rating: DC | 28 VDC / 600 watt |
Output voltage regulation: | ± 2.0% static regulation of nominal |
Overload surge capacity: | 110% continuously |
Output protection: | Front panel mounted fuse (DC) |
AC INPUT | |
Input voltage selection: | Dual Source Input, two separate AC sources, J1A and J1B Nominal 115 VAC, optional autoranging input of 85-270 VAC |
Input voltage tolerance: UPS | 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load |
Input frequency: | From 46 Hz to 70 Hz standard, optional to 440 Hz |
Input power factor: | Better than 99% typically |
Input/output isolation: | 2000 VA, up to 120 dB common mode, <1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole switch (S1) w/fuse (F2A and F2B) Cold start to turn on w/o AC present |
Input power connections: | Two MS 3102A-22-2P, 3 pin, locking |
EXTERNAL BATTERY | |
External battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
External battery life: | Rated for continuous service life of 5 years |
External DC protection: | Front panel mounted fuse (F1) |
Battery expansion: | Up to 24 hours w/ Battery Expansion Modules |
DISTRIBUTION PANEL | |
Output circuits: | One AC and two DC outputs standard |
Output control: | Optional remote control panel w/rocker switches |
Output receptacles: AC output DC output |
MS3102A22-2S, 3 pin locking standard, various options MS3470W14-5S, 5 pin locking standard |
MECHANICAL | |
Dimensions (H x D x W): UPS Battery Module |
5.25 (3U) x 23.5 x 19.0 in (133 x 597 x 483 mm) 3.50 (2U) x 23.5 x 19.0 in (89 x 597 x 483 mm) |
Rack Slide Mount Patterns: | Jonathan, General Devices patterns, others optional |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: UPS Module Battery Module |
95 lb. (43 kg) UPS with lift handles front and rear 102 lb. (46 kg) Battery with lift handles front and rear |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, positive pressure, forced air |
Cooling air direction: | Rear intake, exhaust to front, others optional |
Air intake filter: | Washable metal filter media, others optional |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: | -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optional |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits |
March 18