LinkedIn




P/N: ETI0003-1171 20 Amp Power Distribution Unit (PDU)

Part Number:
ETI0003-1171
Rugged Rackmount Power Distribution Unit
with UPS Interface and Remote Control


Navy IT-21, BGPHES,SPAWAR Standard Product
Ultra Compact, Backward Compatible Configuration with UPS Interface
20 Amp Rugged Rack Mount PDU w/ 6 Circuit, 2 Pole,
Intelligent, Solidstate Controls and Remote Control Panel
Safety, Thermal and UPS Interlocks

<br />ETI0003-1171 Front Panel View

ETI0003-1171 Standard Front Panel Layout (w/ Remote Control Panel off)

<br />ETI0003-1171 Rear Panel View

ETI0003-1171 Standard Rear Panel Layout

The field proven Rugged Systems™ Power Distribution Unit (PDU) line is ideally suited for military, industrial and telecommunicationsapplications requiring a rugged rack, vehicular or field deployable, high reliability, compact sizeand light weight design. The heavy-duty chassis occupies only 1U (1.75”) ofrack space while controlling up to 2400 VA of power via six double polecontrols. Therounded metal corners and rugged handles aid in safehandling. Internally, all major components are well secured and electricallyinsulated to prevent damage due to shock and vibration. All controlsand protective devices are brought to the front panel with critical switches orbreakers guarded. Further, all front panel devices are recessed to preventdamage or accidental operation. The control panel contains individual controlbreakers, alarm silenceswitch and alarm LEDs.

The LEDarrays keep the operator informed as to the unit's status. An alarm will flashits respective LED until acknowledged. Once the alarm reset is pressed, the LEDwill remain on steady until the alarm is cleared. The intelligent PDU allows control ofthe individual output circuits incorporating thermal and interlock interfacesfor additional control and safety, plus Battleshort override. Each loadcan have an external interlock toturn off power to equipment when it is not fully engaged in the rack or becomesoverheated. The rack may be equipped with both a thermal warning and a thermal shutdown sensor that thePDU uses to alarm and shut down all the loads to avoid damage or thermalrunaway. A Battleshort signalwill override both the thermal and interlock signals. An external Fan Fail orauxiliaryalarm signal can also brought in to annunciate. The high intensity audible alarm can be heard in high noiseenvironments, yet is easily adjustable to suit quieter conditions. The double pole inputbreaker provides overload and short circuit protection for the connected UPS inputisolation transformer and rack fans. The PDU input circuit breaker on/off operation is also interlocked to control the UPS on/offfunction as well. Power from the UPS is brought back to the PDU to bedistributed to the loads. Eachload is controlled and protected by both a double pole shock rated circuitbreaker and by a double pole solidstate relay

Therear panel provides locking connectors for the input power, output power, alarmand control signals. Appropriate jumper plugs are available for options notused in a particular rack system.

Overall, the Rugged Power product line is uniquely qualified for critical shipboard,vehicle, airborne or land based systems combining advanced modular designfeatures with highly reliable construction.

Technical Specifications:

ETI0003-1171

AC INPUT FROM RACK
PDU input from rack: 120 VAC nominal, optional up to 600 VAC
INPUT MAIN (J11) connection: MS3474W18-8P, 8 pins, locking
Input protection/control: Guarded 2 pole, 20 amp circuit breaker
Input power indicator: Green neon lamp
AC OUTPUT TO UPS
PDU output to UPS: Same as input from rack
AC TO UPS (J11) connection: Uses same connector as input from rack
AC INPUT FROM UPS
PDU input from UPS: 120 VAC, 60 Hz nominal, standard UPS
AC FROM UPS (J10) connection: MS3474W14-4P, 4 pins, locking
AC OUTPUT TO FANS
PDU output to fans: Same as input from rack
AC TO FANS (J12) connection: MS3474W16-8S, 8 sockets, locking
POWER DISTRIBUTION
PDU output voltage to loads: 120 VAC, 60 Hz nominal, standard UPS
Output rating to loads: Limited to lesser of 20 amps or UPS rating
Output circuits: Six controlled outputs w/2 pole ss relays
Output protection: Guarded individual 2 pole circuit breakers
CNTRLD AC OUT 1-5 (J13) connection: MS3474W20-16S, 16 sockets, locking
CONTROLLED AC OUT 6 (J3) connection: MS3474W14-5S, 5 sockets, locking
THERMAL CONTROL
Control function: Two stage thermal warning and shutdown
THERMAL CONTROL (J6): AMP 206705-1, 9 pins, locking
INTERLOCK CONTROL
Control function: Microswitches sense each equipment position
Disconnects power to load when racked out
INTERLOCK (J8) connection: AMP 206036-1, 16 pins, locking
REMOTE CONTROL
Output control/alarm silence: Local/remote control panel w/rocker switches
Operational status: LEDs for LOW BATT, AC FAIL, WARM, HOT, CPU
Adjustable +90 dB audible alarm
REMOTE CONTROL (J9) connection: MS3474W14-18S, 18 sockets, locking
UPS INTERFACE
Control function: AC Fail & Low Battery signals, UPS on/off control
UPS (J7) connection: AMP 206043-1, 14 sockets, locking
MECHANICAL
Dimensions ( H x D x W ): 1.75 (1U) x 14.9 x 19.0 in (44x378x483mm)
Rack Slide Mount Patterns: Slides or rear support mounting brackets
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Shipping weight: 20 lb. (9.1 kg) with lift handles front
Audible noise: Less than 47 dB @ 5.0 ft., ANSI "A" scale
Cooling type: Convection cooling
ENVIRONMENTAL
Storage temperature: -13° to 140° F ambient (-25° to 60° C )
Operating temperature: 32° to 122° F ambient (0° to 50° C ),higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Operating elevation: Up to 15,000 ft (4,572 m), higher optionally
STANDARDS
United States: Meets UL-1778 standard,
MIL STDs 901, 167 & 1399 Shock/Vib/Electrical
Canada: CSA C22.2 No. 107 safety requirements
EMI Protection: EMI/RFI FCC, Class B, MIL STD 461 
OPTIONAL ACCESSORIES
  Dual Source Input, Emergency Power Off, EMI Insertion Loss Filters, Auxiliary DC Power Supply, MS Connectors, Transient Surge Suppression, Load Sequencing
Contact Us for a Free Quote
*(denotes required field)
Contact ETI by mail at:
Energy Technologies, Inc.
219 Park Avenue East
Mansfield, OH 44902-1845
USA

Contact ETI by phone or fax:
Voice: 419-522-4444
FAX: 419-522-4466