Part Number:
ETI0001-2275
Extreme Environment 2000 VA UPS
Fixed Mount or Rackmount
2 kVA Extreme UPS® w/ Input PFC, Manual Bypass and Self Test
Used in Extreme Temperature Environments including
Outdoor Shelters and Switchgear Applications
Supports Computers and Harsh Inductive Loads at the Same Time
Rugged Fixed Mount or Rackmount Unit
ETI0001-2275 Rugged Mil Spec UPS Standard Front Panel Layout
ETI0001-2275 Rugged Mil Spec UPS Standard I/O Panel Layout
The field proven Extreme UPS® line is ideally suited for industrial, military, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in locations with controlled or uncontrolled environments including fixed,field deployed, vehicular, shipboard or airborne. For example, thousands of "
ETI0001-2275" units are being used in the switchgear of wind turbine generators around the world. In this application, the output supports both a computer type load and operates large inductive switchgear contactors at the same time. This places extreme demands in electrical performance that causes most other vendors' UPS products to fail. In the case of the
ETI0001-2275, it is able to provide the large surge currents required to operate the contactors without dropping the voltage and loosing the computer load!! On top of this, the equipment operates in harsh temperature environment ranging from as low as -40° Fahrenheit (-40° Celsius) toas high as 149°Fahrenheit (65° Celsius).
The heavy-duty chassis, occupying minimal space while delivering up to 2000 VA of clean, uninterruptible power. Therounded metal corners and rugged handles, aid in safe handling. Internally, all major components are wellsecured and electrically insulated to prevent damage due to shock andvibration. These units can be mountedhorizontally or vertically. Optional heavy-duty rack slides provideeasy installation and removal of the unit with full extension.
The internal shielded input transformerprovides galvanic isolation with provisions for both domestic(115 VAC, CONUS) and international (230 VAC, OCONUS) input voltages. Theoptional autoranging input voltage selection allows inputting either 115 VAC or 230 VAC without having to open the UPS enclosure.These units work equally well from all AC sources including poorly regulated generators. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to clean, uninterruptible 60 hertz power. The input switch and the galvanic isolation transformer all provide a double pole isolated source for shipboard systems or overseas locations where phase references and grounding are not always consistent. The nominal 120 VAC, 60 hertz output can be field set for 100, 110 or 115 VAC. An alternate version is also available for 200-240 VAC, 50 hertz output.
All controls and protective devices are brought to the outer panels with critical switches or circuit breakers having finger guards. Further, all critical deviceshave finger guards to prevent damage or accidental operation. The LED arrays keep the operatorinformed as to the unit's status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. The internal intelligent thermal sensors provide monitoring of unit temperatures. The optional ElapsedTime Indicator records the number of operational hours for records andscheduling preventative maintenance of attached equipment. The front panel alsoprovides easy access to both the AC Input circuit breakerand Battery Input fuse. Coupled withthe onboard spare fuse, MTTR is reduced to less than 15 minutes.
Theinput circuit breaker and the galvanic isolation transformerall provide a double pole isolated source for all installations including shipboard systems oroverseas locations where phase references and grounding are not consistent. Themanual bypass feature included is operated from the front panel. Even in thebypass mode, the
ETI0001-2275 stillprovides galvanic isolation, transient surge protection and EMI/RFI filtering. The unit also has a self test feature that can be initiated by the operator from the front panel.
The
ETI0001-2275 has the added benefit of having a field replaceable battery tray. Even with this batterytray removed, this UPS can continue to operate as an electronic power conditioner and frequency converter, providing clean, well regulated, sinusoidal power to the load. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials for added safety. For more information, see the Battery Technology section.
Removable and washable air filters and a high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments. Thisunit draws air through the intake filters and exhausts out the rear or side vents.This allows the unit to be used in negative or neutral pressure racks. Forpositive pressure systems, other versions are available. The removable and washable metal screen air filters and high capacity stainless steel ball bearing fans provideadded protection in both controlled and hostile environments.
The I/O panel provides locking connectors for the input and output power. Multiple input and output power panel options are available. The exhaust air is diverted out the rear vent, with alternate air flow directions optional. See the Power Distribution Units section for alisting of stand alone PDUs. See the N5 Series section forversions of UPS with an integrated PDU and remote control.The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
Overall, the Extreme UPS®line is uniquely qualified for critical land based, shipboard, vehicle or airborne systems combining advanced modular designfeatures with highly reliable construction.
AC OUTPUT | |
Output voltage: | Nominal 120 VAC true sinewave output standard, optional 220 VAC version |
Output voltage adjustment: | Can be set for 100, 110, 115 or 120 VAC via DIP switches |
Output rating: UPS | 2000 VA, 1400 watts standard Available in 1000, 1500, 2000 and 3000 VA ratings |
Non-linear load capacity: UPS | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: UPS | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: UPS | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 2.5% synchronized to utility 60 Hz ± 1.0% w/ utility not available 50 Hz output available as an option |
Operational status | AC Input status, UPS operational, UPS alarm, Battery level, Low battery, Load level, Overload and Manual bypass LEDs, Alarm contacts for Loss of AC and Low Battery +90 dB audible alarm with audible on/off switch & over temp. alarm. Contact Closure or Asynchronous serial COM port, optional SNMP/HTTP |
AC INPUT | |
Input voltage selection: | 120 VAC nominal (87-140V) or 220 VAC nominal (87-240V) |
Input voltage tolerance: UPS | +15% -25% @ full load without using battery |
Input frequency: | From 46 Hz to 70 Hz standard, optional to 440 Hz |
Input power factor: | Better than 95% typically |
Input/output isolation: | 2000 VA, up to 120 dB common mode, <1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587, UL 1449 and Mil Std 1399 |
Input control/protection: | Guarded 2 pole 100 G shock rated circuit breaker (CB1) Internal feature of cold start to turn on w/o AC present |
Input power connections: | One (1) AMP CPC, 3 pin, locking |
INTERNAL BATTERY | |
Internal | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Internal | Rated for continuous service life of 5 years |
Internal | Front panel mounted fuse (F1), spare fuse on front |
Internal battery time: | 15+ minutes @ full load 30+ minutes at 50% load |
Internal battery recharge: | Recharged to nominal in <8 hours |
Internal battery replacement: | Battery module tray from top of unit <30 minutes to change battery modules |
Battery expansion: | Up to 24 hours w/ optional Battery Expansion Modules |
DISTRIBUTION PANEL | |
Output circuits: | Three (3) AC outputs standard, several optional configurations |
Output control: | Only via CB1; optional remote control panel w/switches available |
Output receptacles: AC output | Two (2) NEMA 5-15R and one (1) AMP CPC standard, various options |
MECHANICAL | |
Dimensions (H x D x W): UPS | 7.0 (4U) x 17 x 15.86 in (178 x 432 x 403 mm) |
Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical (Mounting Brackets Included) |
Unit weight: UPS and Battery UPS only Battery Module only |
112 lb. (51 kg) with lift handles 70 lb. (32 kg) with lift handles 42 lb. (19 kg) with lift handle |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, negative pressure, forced air |
Cooling air direction: | Side intake, exhaust to opposite side |
Air intake filter: | Washable foam or metal filter media options |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries with fully charged batteries |
Operating temperature: | 32° to 122° F ambient ( 0° to 50° C), -40° to 149° F ambient ( -40° to 65° C) optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optional |
STANDARDS | |
United States: | ETL Listed to UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; optional MIL STD 461 |
OPTIONAL ACCESSORIES | |
Emergency Power Off, Alternate I/O Configurations, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits |