Part Number:
ETI0001-2221
NSN: 6130-01-537-3889
Rugged Mil Spec® Rack or Fixed Mount
2200 VA UPS Both AC and DC Outputs
Hot Swappable Batteries
US Navy AN/WDL-1 Mine Sweeper Standard Product
2.2 kVA Mil Spec UPS w/ AC and DC Outputs
Rugged Rack or Fixed Mount Unit
w/ Reduced Depth and Removable Battery Modules
ETI0001-2221 Rugged Mil Spec UPS Standard Front Panel Layout
NSN: 6130-01-537-3889
ETI0001-2221 Rugged Mil Spec UPS Standard Rear Panel Layout
The field proven Military Power® UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, ruggedconstruction, compact size and light weight design. These units are equallysuited for use in shipboard, airborne, vehicular, field deployed or fixedlocations with controlled or uncontrolled environments. The"
ETI0001-2221" is being used by the US Navy on the WLD-1 project becauseof their stringent performance and reliability requirements.
The heavy-duty chassis,occupying only 10.5" (6U) of rack space and 19" depth, has rounded metal cornersand rugged handles front and rear, aiding in safe handling. Internally, all majorcomponents are well secured and electrically insulated to prevent damage due to shock andvibration.
The internal shieldedinput transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) inputvoltages. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The unit also operatesas a frequency converter, taking 46-440 hertz input and converting it to clean,uninterruptible 60 hertz power. The input switch and the galvanic isolationtransformer all provide a double pole isolated source for all installations including shipboardsystems or overseas locations where phase references and grounding are notconsistent.
The LED arrays keep theoperator informed as to the unit's status including load and battery levels. Thehigh intensity audible alarm can be heard in high noise environments. All controlsand protective devices are brought to the front and rear panels with critical switches having fingerguards. Further, all front panel devices are recessed to prevent damage or accidentaloperation. Variousoptional power distribution controls are available which mount on the front panel orremotely.
The rear panel provides barrier terminalblocks for the input and outputpower. Multipleinput and output power panel options are available. Removable and washable air filters and a high capacity stainless steel ball bearing fans provideadded protection in both controlled and hostile environments. The exhaust air is diverted out therear vent, with alternateair flow directions optional. The "
ETI0001-2221" has the added benefit of havingfield replaceable batteries via a front drawout battery modules. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. The Status connector provides aninterface with optional computer software providing loss of AC and low battery status as well asremote shut down capability.
See the Power Distribution Units section for alisting of stand alone PDUs. See the N5 Series
ETI0001-1482for a version of this UPS with an integrated PDU and remote control.
Overall, the Rugged Power line is uniquely qualified for criticalshipboard, vehicle, airborne or land based systems combining advanced modular designfeatures with highly reliable construction.
OUTPUTS | |
Output voltage: UPS AC: UPS DC: |
120 VAC true sinewave standard 28 VDC isolated 28 VDC isolated 28 VDC isolated |
Output rating: UPS Total: DC Outputs: |
2200 VA total including DC outputs, up to 1500 VA AC 5 amps @ 28 VDC 11 amps @ 28 VDC 15 amps @ 28 VDC respectively |
Non-linear load capacity: UPS | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: UPS | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: UPS | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 1.0% independent of input frequency 50, 400 or 1000 Hz output available as an option |
Operational status | Status, load and battery LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT | |
Input voltage selection: | Nominal 115 VAC, optional autoranging input of 85-270 VAC |
Input voltage tolerance: UPS | 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load |
Input frequency: | From 46 Hz to 440 Hz standard |
Input power factor: | Better than 99% typically |
Input/output isolation: | 2200 VA, up to 120 dB common mode, <1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole toggle circuit breaker |
Input power connection: | Barrier terminal block |
INTERNAL BATTERY | |
Internal battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Internal battery life: | Rated for continuous service life of 5 years |
Internal DC protection: | Front panel mounted fuse standard, breaker optional |
Internal battery time: | 30+ minutes @ 100% load, 60+ minutes @ 50% |
Internal battery recharge: | Recharged to nominal in <8 hours |
Internal battery replacement: | (2) Drawout/plug-in modules from front of unit |
DISTRIBUTION PANEL | |
Output circuits: | Four outputs standard, optional configurations |
Output control: | Guarded toggle circuit breakers |
Output receptacles: | Barrier terminal blocks |
MECHANICAL | |
Dimensions ( H x D x W ): | 10.5 (6U) x 19.1 x 19.0 in (267 x 485 x 483 mm) |
Rack Slide Mount Patterns: | Jonathan, General Devices patterns, others optional |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: UPS w/o Battery Internal Battery Module |
95 lb. (43 kg) UPS with lift handles front and rear 64 lb. (29 kg) Each Battery Module |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, positive pressure, forced air |
Cooling air direction: | Front intake, exhaust to rear, others optional |
Air intake filter: | Washable metal filter media, others optional |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: | -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optional |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Cold Start, Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits |