P/N: ETI0001-1482 2.0 kVA Rugged Rackmount MilSpec UPS with Internal Intelligent PDU, NSN: 6130-01-570-9215

Part Number:
ETI0001-1482 
NSN: 6130-01-570-9215
Rugged Mil Spec
® 2000 VA Integrated
Rackmount UPS and Intelligent
Power Distribution Unit Combination


L3 Comm / Navy Military Power® Mil Spec N5Configuration
2000 VA Rugged Rack MountIsolated UPS w/ Integrated
6 Circuit, 2 Pole, Intelligent, Solidstate Power Distribution Unit
With Drip Proof Front Panel, Shallow Depth, Removable Battery

P/N: <br />ETI0001-1482 Rugged MilSpec UPS and PDU Standard Front
P/N:
ETI0001-1482 Rugged Mil Spec UPS andPDU Standard Front 
Panel Layout

NSN: 6130-01-570-9215

P/N: <br />ETI0001-1482 Rugged MilSpec UPS and PDU Standard Rear 
P/N:
ETI0001-1482 Rugged Mil Spec UPS andPDU Standard Rear 
Panel Layout

<br />ETI0001-0876 Front View
Optional P/N:
ETI0001-0876 UPS and PDU Remote Control Panel in 1U

The field proven Military Power® UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.These units are equally suited for use in shipboard, airborne, vehicular, fielddeployed or fixed locations with controlled or uncontrolled environments. The
ETI0001-1482 was specifically designed for US Navy Submarine systemsrequiring high density power in shallow depth racks.The
ETI0001-1482 does not require a separate PDU since the PDUfunctions are already integrated into the UPS module. This saves rack space,cabling and expense while improving overall reliability. 

The heavy-duty chassis occupies only 4U (7.0”) ofrack space and is only 18.5" deep making it suitable for shallow racks asfound on submarines. The front panel is sealed meeting the Navy drip proofrequirements. Therounded metal corners and rugged handles, both front and rear, aid in safehandling. Internally, all major components are well secured and electrically insulated to preventdamage due to shock and vibration in any axis. These units can be mountedhorizontally or vertically.

The internal shieldedinput transformer provides galvanic isolation with provisions for both domestic(115 VAC, CONUS) and optional autoranging international input voltages (85-270 VAC,OCONUS). Theunit also operates as a frequency converter, taking 46-70 hertz input and converting it to 60 hertz power. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The inputcircuit breaker and the galvanic isolation transformerall provide a double pole isolated source for all installations including shipboard systems oroverseas locations where phase references and grounding are not consistent. 

The LEDarrays keep the operator informed as to the unit's status including load andbattery levels. The ElapsedTime Indicator records the number of operational hours for records andscheduling preventative maintenance of attached equipment. The high intensity audible alarm can be heard in high noiseenvironments. All controlsand protective devices are brought to the front and rear panels with critical switches orbreakers guarded. Further, all front panel devices are recessed to preventdamage or accidental operation. The internal intelligent PDU allows control ofthe individual output circuits incorporating thermal and interlock interfacesfor additional control and safety, plus Battleshort override. The display andcontrol panel can be mounted remotely in the rack at eye level, or on the keyboardconsole with only a logic level cable connection. 

The rear panel provides locking connectors for the input and output power with various optional configurations available. The output connectors are unique allowing the use of either standardNEMA 5-15P plugs or MS threaded metal shell connectors. Thisunit draws air through the rear air filter and exhausts out the side vents into the rack.This allows the unit to be used in either positive, negative or neutral pressureracks. The removable and washable metal screen air filters and high capacity stainless steel ball bearing fans provideadded protection in both controlled and hostile environments. The
ETI0001-1482 has the added benefit of having afield replaceable battery via a rear drawout battery module. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. The Status connector provides aninterface with optional computer software providing loss of AC and low battery status as well asremote shut down capability. The UPS Remote Control and the PDU Remote Control connectorsprovide aninterface to optional remote display/control panels. 

See the Power Distribution Units section for a listing of stand alone PDUs. See the N3 Series UPS section for UPS withoutthe integrated PDU and remote control.

Overall, the Military Power line is uniquely qualified for critical shipboard,vehicle, airborne or land based systems combining advanced modular designfeatures with highly reliable construction.

Technical Specifications:
P/N:
ETI0001-1482
NSN: 6130-01-570-9215

AC OUTPUT
Output voltage: 120 VAC true sinewave standard, others optional
Output rating: UPS 2000 VA standard in 4U chassis x 18.5" deep 
0.65-0.75 pf standard, optional configurations to 24,000 VA
Non-linear load capacity: Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 Hz ± 2.5% synchronized to utility
60 Hz ± 1.0% w/ utility not available
400 or 1000 Hz output available as an option
Operational status Status, load and battery level LEDs, w/contacts
Adjustable level,+90 dB audible alarm w/on/off
AC INPUT
Input voltage selection: Nominal 115 VAC, optional autoranging input of 85-270 VAC
Input voltage tolerance: UPS 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load
Input frequency: From 46 Hz to 70 Hz standard, optional to 440 Hz
Input power factor: Better than 99% typically
Input/output isolation: 2000 VA, up to 120 dB common mode, <1.0 mA leakage
Input transient suppression: Complies with IEEE 587 and UL 1449
Input control/protection: Guarded 2 pole 100 G shock rated breaker w/ UPS fuse
Optional cold start to turn on w/o AC present
Input power connection: MS 3102A-22-2P, 3 pin, threaded locking
INTERNAL BATTERY
Internal battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
Internal battery life: Rated for continuous service life of 5 years
Internal DC protection: Panel mounted fuse standard, breaker optional
Internal battery time: 15 minutes @ 1300 watts (2000 VA @ 0.65 pf, typical full load for computers),
10 minutes @ 1500 watts load (maximum wattage), 35 minutes @ 50% load
Internal battery recharge: Recharged to nominal in 8 hours
Internal battery replacement: Drawout/plug-in module from front of unit
DISTRIBUTION PANEL
Output circuits: Six controlled outputs via solidstate relays
Output control: Local/remote control panel w/rocker switches
Thermal and remote interlock ON/OFF control
Output receptacles: MS / NEMA 5-15R threaded locking, various options
MECHANICAL
Dimensions ( H x D x W ): 7.0 (4U) x 18.5 x 19.0 in (178 x 470 x 483 mm)
Rack Slide Mount Patterns: Jonathan, General Devices patterns standard, others optional
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Shipping weight: Total
  UPS w/o Battery Module
  Drawout Battery Module
169 lb. ( 77 kg) with lift handles front and rear
105 lb. ( 48 kg) with lift handles front and rear 
  64 lb. ( 29 kg) with lift handles rear
Audible noise: Less than 47 dB @ 5.0 ft., ANSI "A" scale
Cooling type: High capacity, positive pressure, forced air
Cooling air direction: Rear intake, exhaust to sides
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C) with fully charged batteries
Operating temperature: 32° to 122° F ambient ( 0° to 50° C), lower/ higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m)
Operating elevation: Up to 15,000 ft (4,572 m), higher optional
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 
OPTIONAL ACCESSORIES
  Autoranging International Input, Cold Start, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port,  Transport Cases, Slides and Mounting Kits
Contact Us for a Free Quote
*(denotes required field)
Contact ETI by mail at:
Energy Technologies, Inc.
219 Park Avenue East
Mansfield, OH 44902-1845
USA

Contact ETI by phone or fax:
Voice: 419-522-4444
FAX: 419-522-4466