TAC-4, ATWCS, Tomahawk and Hewlett Packard StandardProduct Standard S1 Configuration, Military Power® Isolated UPS
Mil Spec 2000 VA Rugged Rack Mount,w/ PFC and Integrated 6 Circuit, 
2 Pole, Intelligent, Solidstate Power Controls and
Remote Power Distribution Units

P/N: <br />ETI0001-1438 Rugged MilSpec UPS Standard Front Panel LayoutP/N:
ETI0001-1438 Rugged Mil Spec UPS Standard Front Panel Layout

P/N: <br />ETI0001-1438 Rugged MilSpec UPS Standard Rear Panel LayoutP/N:
ETI0001-1438 Rugged Mil Spec UPS Standard Rear Panel Layout

Rugged 1U Remote Distribution Unit w/ IEC 320-15RP/N:
ETI0003-1201 Remote Distribution Unit w/ IEC 320-15R

Rugged 1U Remote Distribution Unit w/ IEC 320-20RP/N:
ETI0003-1202 Remote Distribution Unit w/ IEC 320-20R

Rugged 1U Remote Distribution Unit w/ NEMA 5-15RP/N:
ETI0003-1203 Remote Distribution Unit w/ NEMA 5-15R 

Rugged 1U Remote Distribution Unit w/ MS NEMA 5-15RP/N:
ETI0003-1206 Remote Distribution Unit w/ MS NEMA 5-15R 

Rugged 1U Remote Distribution Unit Top ViewTop View of Typical Remote Unit Showing Shallow Depth

The field proven Military Power® UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.These units are equally suited for use in shipboard, airborne, vehicular, fielddeployed or fixed locations with controlled or uncontrolled environments.The
ETI0001-1438 was specifically designed to mountin the TAC-4 style racks BUT does not require a separate PDU as in TAC-4.The PDU functions are already built-in. The 1U Remote Distribution Units can belocated anywhere in the rack (rear, dead space) in any orientation (horizontalor vertical). This saves rack space, cable lengths are reduced, cable handlerseliminated, saving expense while improving overall reliability.

The heavy-duty chassis occupies only 3U (5.25") of rack space while delivering up to2000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles, aidin safe handling. Internally, all major components are well secured and electricallyinsulated to prevent damage due to shock and vibration. The optional heavy-duty rack slides provideeasy installation and removal of the unit with full extension. Rear shockisolation/alignment bushings off load the slides when the unit is fully engaged.

The internal shieldedinput transformer provides galvanic isolation with provisions for both domestic (115 VAC, CONUS) and international (230 VAC, OCONUS) inputvoltages. The input voltage selection is automatic without having to open the UPS enclosure. The input switchand the galvanic isolation transformerall provide a double pole isolated source for all installations including shipboard systems oroverseas locations where phase references and grounding are not consistent. 

The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm canbe heard in high noise environments.All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to preventdamage or accidental operation. The internal intelligent PDU allows control ofthe individual output circuits incorporating thermal and interlock interfacesfor additional control and safety, plus Battleshort override. The display andcontrol panel can be mounted remotely in the rack, or on the keyboard console,or on the unit front panel with only a logic level cable connection. 

The rear panel provides locking connectors for the input and outputpower. This reverse air flow version draws air through the front and exhausts out the rearvent into the rack. A removable and washable intake air filter and high capacity stainless steel ballbearing fan provide added protection in both controlled and hostile environments. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. The two status D shell connectors provide both a contact and serial interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

See the Power Distribution Units section for a listing of stand alone PDUs. See the N3 Series
ETI0001-1237
for a version of this UPS without the integrated PDU and remote control.

Overall, the Military Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.

Technical Specifications:
P/N:
ETI0001-1438

AC OUTPUT
Output voltage: UPS 120 VAC true sinewave standard, up to 600 VAC optional
Output rating: UPS 2000 VA standard in 3U chassis
0.65-0.75 pf standard, optional configurations to 24,000 VA
Non-linear load capacity: UPS Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: UPS 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: UPS Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz output available as an option
Operational status Status, load and battery LEDs, w/contacts
RS-232 asynchronous serial status COM port
Adjustable level,+90 dB audible alarm w/on/off
AC INPUT
Input voltage selection: Autoranging from nominal 115 VAC to 230 VAC
Input voltage tolerance: UPS 85-270 VAC @ full load without using battery, to 70 VAC @ 75% load
Input frequency: From 46 Hz to 70 Hz standard, optional to 440 Hz
Input power factor: Better than 99% typically
Input/output isolation: 2000 VA, up to 120 dB common mode, <1.0 mA leakage
Input transient suppression: Complies with IEEE 587 and UL 1449
Input control/protection: Guarded 2 pole input breaker w/ UPS fuse
Optional cold start to turn on w/o AC present
Input power connection: MS 3102A-22-2P, 3 pin, threaded locking
INTERNAL BATTERY
Battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
Battery life: Rated for continuous service life of 5 years
DC protection: Panel mounted fuse standard, breaker optional
Battery time: 15+ minutes @ 100% load,30+ minutes @ 50%
Battery recharge: Recharged to nominal in <8 hours
DISTRIBUTION PANEL
Output circuits: (1) AMP MCPC locking feeding to Remote Distribution
Output controls: (1) DE9 feeding to Remote Distribution Unit
REMOTE DISTRIBUTION UNIT
Input circuits: (1) AMP MCPC locking coming from UPS
Input controls: (1) DE9 coming from UPS
Output circuits: Six controlled outputs via solidstate relays
Output control: Local/remote control panel w/rocker switches
Thermal and remote interlock ON/OFF control
Output receptacles: P/N:
ETI0003-1201 has IEC 320-15R w/cable bales
P/N:
ETI0003-1202 has IEC 320-20R
P/N:
ETI0003-1203 has NEMA 5-15R w/cable bales
P/N:
ETI0003-1204 has NEMA 5-15R (duplex)
P/N:
ETI0003-1205 has NEMA L5-15R twist locks
P/N:
ETI0003-1206 has Metal Shell NEMA 5-15R
MECHANICAL
Dimensions ( H x D x W ):
UPS
Remote Distribution Units
5.25 (3U) x 28.0 x 19.0 in (133 x 711 x 483 mm)
1.75 (1U) x 3.0 x 19.0 in (44 x 76 x 483 mm)
Rack Slide Mount Patterns: Actron / Jonathan slide pattern standard, others optional
Rack rear alignment pins: (2) shock isolation/alignment pin/socket sets
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight: 155 lb. (70 kg) with lift handles front
Audible noise: Less than 47 dB @ 5.0 ft., ANSI "A" scale
Cooling type: High capacity, negative pressure, forced air
Cooling air direction: Front intake, exhaust to rear, others optional
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C) with fully charged batteries
Operating temperature: -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m)
Operating elevation: Up to 15,000 ft (4,572 m), higher optional
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 
OPTIONAL ACCESSORIES