Part Number:
ETI0001-1402 Model:
ETI0001-N5-I/1.5
Rugged COTS1550 VA Rackmount
UPS with Integrated Intelligent Power
Distribution Unit Combination
Navy IT-21, SNAP III, JMOC, ADNS, MAST,SPAWAR Standard Product Standard N5 Configuration, Rugged Power™Isolated UPS, 1550 VA Rugged Rack Mount UPS w/ Integrated
6 Circuit, 2 Pole, Intelligent, Solidstate Power Distribution Unit
NSN: 6130-01-434-3701
ETI0001-1402 Rugged COTS UPS and PDU Standard Rear Panel Layout
NSN: 6130-01-434-3701
ETI0001-1402 Rugged COTS UPS and PDU Standard Rear Panel Layout
N5 Standard RemotePanel OptionalN5 Remote Panel w/ EPO
The field proven Rugged Systems™ UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.These units are equally suited for use in shipboard, airborne, vehicular, fielddeployed or fixed locations with controlled or uncontrolled environments. The"N5 Series" was specifically designed to save rack space andinstallation costs while enhancing the functionality of both the UPS and PDU.The "N5 Series" does not require a separate PDU since the PDUfunctions are already integrated into the UPS module. This saves rack space,cabling and expense while improving overall reliability.
The heavy dutychassis occupy only 3U of rackspace while delivering up to 1550 VA of clean, uninterruptible power. The roundedmetal corners and rugged handles, both front and rear, aid in safe handling. The optionalmounting kit includes flanges and legs for either horizontal or vertical positioning.Internally, all major components are well secured and electrically insulated to preventdamage due to shock and vibration. An internal transformer bay accommodates the inputisolation transformer with provisions for both domestic and optional internationalvoltages. The LED arrays keep the operator informed as to the unit's status including loadand battery levels. The high intensity audible alarm can be heard in high noiseenvironments, yet is easily adjustable to suit quieter conditions. All controls andprotective devices are brought to the front panel with critical switches or breakersguarded. Further, all front panel devices are recessed to prevent damage or accidentaloperation.
The internal intelligent PDU allows control ofthe individual output circuits incorporating thermal and interlock interfacesfor additional control and safety, plus Battleshort override. The display and control panel can be mounted remotely in the rack or on thefront panel with only a logic level cable connection. The inputcircuit breaker and the galvanic isolation transformerall provide a double pole isolated source for all installations including shipboard systems oroverseas locations where phase references and grounding are not consistent.
The rear panel provides locking connectors for the input and output power. A washableintake air filter and high capacity stainless steel ball bearing fans provide added protection in bothcontrolled and hostile environments. Typically the exhaust air is diverted out the front vents, oreasily changed to vent out the sides or both. The external battery connector allows the safe and easy addition ofthe standard or extra battery modules without having to shut the unit down.The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. Afrequency selection switch is available for those sites requiring 50 hertz output insteadof the standard 60 hertz.The status D shell connector provides aninterface with optional computer software providing loss of AC and low battery status as well asremote shut down capability.
See the Power Distribution Units section for a listing of stand alone PDUs. See the N3 Series UPS section for UPS withoutthe integrated PDU and remote control.
Overall, the Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction
Technical Specifications:
P/N:
ETI0001-1402
NSN: 6130-01-434-3701
AC OUTPUT | |
Output voltage: | 120 VAC true sinewave standard, others optional |
Output rating: UPS | 1550 VA in 3U chassis 0.65-0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 or 50 Hz ± 2.5% synchronized to utility 60 or 50 Hz ± 1.0% w/ utility not available 400 or 1000 Hz output available as an option |
Operational status | Status, load and battery level LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT | |
Input voltage selection: | Nominal 115 VAC, optional autoranging input of 85-270 VAC |
Input voltage tolerance: UPS | 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load |
Input frequency: | From 46 Hz to 70 Hz standard, optional to 440 Hz |
Input/output isolation: | Up to 2000 VA, up to 120 dB common mode, <5 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole input circuit breaker CB1 plus fuse F2 Optional cold start to turn on w/o AC present |
Input power connection: | AMP CPC Type XII locking, various options |
BATTERY | |
Battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Battery life: | Rated for continuous service life of 5 years |
DC protection: | Panel mounted fuse, optional breaker |
Battery expansion: | Up to 24 hours w/ Battery Expansion Modules |
DISTRIBUTION PANEL | |
Output circuits: | Six (6) controlled outputs via solidstate relays |
Output control: | Local/remote control panel w/rocker switches Thermal and remote interlock ON/OFF control |
Output receptacles: | IEC320-15R w/cord restraints, various options |
MECHANICAL | |
Dimensions ( H x D x W ): | 5.25 (3U) x 23.5 x 19.0 in (133 x 597 x 483 mm) |
Rack Slide Mount Patterns: | Jonathan, General Devices patterns standard, others optional |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: | 115 lb. (52 kg) with lift handles front and rear |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, positive pressure, forced air |
Cooling air direction: | Rear intake, exhaust to front or sides or both |
Air intake filter: | Washable filter media, various porosities |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: | 32° to 113° F ambient (0° to 45° C ), lower/higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optionally |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D, 1399-300A, & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A standard; MIL STD 461 optional |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Emergency Power Off, Elapsed Time Meter, Cold Start, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits |