ETI0001-1255, Lockheed Martin/US Navy Trident 99, Rugged Rack Mount 1.5 kVA UPS with Water Proof Front, Reduced Depth and Removable Battery Module
Part Number: |
AC OUTPUT | |
Output voltage: | 120 VAC true sinewave std, up to 600 VAC optional |
Output rating: UPS | 1550 VA, standard in 4U x 19" chassis 0.65-0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 1.0% independent of input frequency 50, 400 or 1000 Hz output available as an option |
Operational status | Status, load and battery LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off Optional asynchronous serial COM port |
AC INPUT | |
Input voltage selection: | Nominal 120 VAC, Optional Autoranging Input of 85-270 VAC |
Input voltage tolerance: UPS | +15% -25%, or 90-138 |
Input frequency: | From 47 Hz to 440 Hz |
Input power factor: | Better than 99% typically |
Input/output isolation: | 2000 VA, 120 dB common mode, <1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole switch (S1) w/fuse (F2) Optional cold start to turn on w/o AC present |
Input power connection: | MS 3102A-22-2P, 3 pin, locking |
INTERNAL BATTERY | |
Internal battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Internal battery life: | Rated for continuous service life of 5 years |
Internal DC protection: | Front panel mounted fuse (F1) |
Internal battery time: | 15+ minutes @ 100% load, 35+ minutes @ 50% |
Internal battery recharge: | Recharged to nominal in <8 hours |
Internal battery replacement: | Drawout/plug-in module from front of unit |
DISTRIBUTION PANEL | |
Output circuits: | Six outputs standard, optional configurations |
Output control: | Optional remote control panel w/rocker switches |
Output receptacles: | Metal shell AMP 208497-1 MCPC, 3 pin locking, other options |
MECHANICAL | |
Dimensions ( H x D x W ): | 7.0 (4U) x 18.5 x 19.0 in (178 x 470 x 483 mm) |
Rack Slide Mount Patterns: | Jonathan, General Devices or Emcor patterns |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: | 95 lb. (43 kg) UPS, 64 lb. (29 kg) Battery |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, positive pressure, forced air |
Cooling air direction: | Rear intake; exhaust to sides |
Air intake filter: | Washable metal filter media, others optional |
ENVIRONMENTAL | |
Storage temperature: | -13° to 140° F ambient (-25° to 60° C) |
Operating temperature: | 32° to 113° F ambient ( 0° to 45° C) |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optionally |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167, 901, 810, 454 & 1399 Shock/Vib/Electrical |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC, Class A; EN55022; MIL STD 461 |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Cold Start, Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits |