ETI0001-1251 1.5 kVA Global UPS, Rugged Rackmount, Vehicle Input, Removable Battery
|
Part Number:
ETI0001-1251
Model:
ETI0001-W1/1.5
NSN: 6130-01-539-4854
Rugged Mil Spec® 1550 VA
Rackmount Global UPS
US Navy / NAWCAD StandardProduct
W1 Configuration, WorldPower™ IsolatedMil Spec UPS
1550 VA Rugged Rack Mount, Modular Power System
Accepts 85-270 VAC, 46-440 Hz Input or 20-32 VDC
Plus a Hot Swappable Battery Module
ETI0001-1251 Rugged Mil Spec UPS Standard Front Panel Layout
ETI0001-1251 Rugged Mil Spec UPS Standard Rear Panel Layout
The field proven WorldPower UPS line is ideally suited for military,industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.These units are equally suited for use in shipboard, airborne, vehicular, fielddeployed or fixed locations with controlled or uncontrolled environments. The
ETI0001-1251 is specifically designed for lightweightglobal power deployment or equally well in shallow depth racks including TAC-4 racks andinterfacing with any of numerous ETIPDUs.
The heavy-duty chassis occupies only 7" (4U) of rack space while delivering up to 1550 VA of clean, uninterruptible power. The rounded metal corners and rugged handles, aidin safe handling. Internally, all major components are well secured and electricallyinsulated to prevent damage due to shock and vibration. The optional heavy-duty rack slides provideeasy installation and removal of the unit with full extension.
The internal shieldedinput transformer provides galvanic isolation with provisions forboth domestic (115 VAC, CONUS) and international (230 VAC, OCONUS) inputvoltages. The autoranging input voltage selection allows inputting either 115 VAC or 230 VAC without having to open the UPS enclosure. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The inputswitch and the galvanic isolation transformer provide a double pole isolated source for all installations including shipboard systems oroverseas locations where phase references and grounding are not consistent.
Alternately, theunit also accepts vehicular or aircraft power from nominal 24 VDC systems. The
ETI0001-1251 has the added benefit of having a front drawout hot-swappable battery module.
The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm canbe heard in high noise environments.All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to preventdamage or accidental operation.
The rear panel provides locking connectors for the input and output power with various optional configurations available. This reverse air flow version draws air through the front and exhausts out the rearvent into the rack. A removable and washable intake air filter and high capacity stainless steel ballbearing fan provide added protection in both controlled and hostile environments. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. The two status D shell connectors provide both a contact and serial interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
See the Power Distribution Units section for a listing of stand alone PDUs. See the N5 Series
ETI0001-1482 for a version of this UPS with an integrated PDU and remote control
Overall, the WorldPower line is uniquelyqualified for critical shipboard, vehicle, airborne or land based systems combiningadvanced modular design features with highly reliable construction.
AC OUTPUT | |
Output voltage: | 120 VAC true sinewave std, up to 600 VAC optional |
Output rating: UPS | 1550 VA, standard in 4U x 19" chassis 0.65-0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 1.0% independent of input frequency 50, 400 or 1000 Hz output available as an option |
Operational status | Status, load and battery (16) LEDs, w/contacts RS-232 asynchronous serial status COM port Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT | |
Input voltage selection: | Autoranging from nominal 115 VAC to 230 VAC |
Input voltage tolerance: UPS | +15% -25%, or 85-135 and 170-270 |
Input frequency: | From 46 Hz to 440 Hz |
Input power factor: | Better than 99% typically |
Input/output isolation: | 2000 VA, 120 dB common mode, <1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole switch (S1) w/fuse (F2) |
Input power connection: | MS 3102A-22-2P, 3 pin, locking |
DC INPUT / INTERNAL BATTERY | |
External DC input: | Nominal 20 to 32 VDC |
External DC control/protection: | Guarded 2 pole switch (S3) w/rear mounted fuse (F3) |
External DC connector: | MS 3102A-24-9P, 2 pin, locking |
Internal battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Internal battery life: | Rated for continuous service life of 5 years |
Internal battery protection: | Rear panel mounted fuse (F1) |
Internal battery time: | 10+ minutes @ 1000 watt load, 20+ minutes @ 50% |
Internal battery recharge: | Recharged to nominal in <8 hours |
Internal battery replacement: | Drawout/plug-in module from front of unit |
DISTRIBUTION PANEL | |
Output circuits: | Six outputs standard, optional configurations |
Output control: | Guarded 3 pole switch (S5) |
Output receptacles: | Metal shell NEMA 5-15R, 3 pin locking, other options |
MECHANICAL | |
Dimensions ( H x D x W ): | 7.00 (4U) x19.0 x 19.0 in (178 x 483 x 483 mm) |
Rack Slide Mount Patterns: | Jonathan, General Devices, others optional |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: | 98 lb. (45 kg) with lift handles front and rear |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, negative pressure, forced air |
Cooling air direction: | Front intake, exhaust to rear |
Air intake filter: | Washable metal filter media, others optional |
ENVIRONMENTAL | |
Storage temperature: | -13° to 140° F ambient (-25° to 60° C) |
Operating temperature: | -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optionally |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC, Class A; EN55022; MIL STD 461 |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Emergency Power Off, Elapsed Time Meter, Cold Start, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, 10BaseT Ethernet SNMP/HTTP port, Transport Cases |